WEBVTT
Kind: captions
Language: en

00:00:00.099 --> 00:00:04.290
If you live in North America, you’re probably
familiar with electrical outlets that have

00:00:04.290 --> 00:00:06.380
a test and reset button.

00:00:06.380 --> 00:00:10.680
Older ones would have red and black buttons,
but newer ones are usually matched to the

00:00:10.690 --> 00:00:12.480
color of the receptacle.

00:00:12.480 --> 00:00:16.090
If you’ve ever messed about with one of
these and pressed the TEST button, you’ll

00:00:16.090 --> 00:00:19.580
have noticed it sort of POP with the RESET
button sticking out a bit,

00:00:19.580 --> 00:00:22.210
and now the outlet is dead.

00:00:22.210 --> 00:00:24.360
To be fair, it told you to test it.

00:00:24.360 --> 00:00:28.440
But now you have to exert quite of bit of
force to shove that reset button back in place

00:00:28.440 --> 00:00:30.660
before the outlet will work again.

00:00:30.660 --> 00:00:31.660
What is this for?

00:00:31.660 --> 00:00:34.809
Why are they usually only found in kitchens
and bathrooms?

00:00:34.809 --> 00:00:36.719
Will I ask a fourth question?

00:00:36.719 --> 00:00:39.750
And how are they, as the title suggests, life-saving?

00:00:39.750 --> 00:00:45.800
Well, this is called (in Americaspeak) a ground-fault
circuit interrupter, or GFCI.

00:00:45.800 --> 00:00:49.580
Sometimes they’re just called Ground-Fault
Interrupters, or GFIs.

00:00:49.589 --> 00:00:54.079
The rest of the world calls them Residual
Current Devices, or RCDs, and usually they

00:00:54.080 --> 00:00:57.910
aren’t found in the bathroom but in the
service panel protecting the entire circuit

00:00:57.910 --> 00:00:59.980
(and sometimes the entire house).

00:00:59.980 --> 00:01:05.300
These simple devices use a fundamental principle
of electricity to detect when an electric shock

00:01:05.300 --> 00:01:09.860
might be in progress, and can nearly
instantly cut power to the circuit to stop

00:01:09.869 --> 00:01:11.740
said electric shock.

00:01:11.740 --> 00:01:15.520
The US electric code requires these outlets
to be fitted when they are within a certain

00:01:15.520 --> 00:01:17.159
distance of a water source.

00:01:17.159 --> 00:01:21.380
That’s why they’re usually found in the
kitchen and bathrooms, though electrical outlets

00:01:21.380 --> 00:01:26.090
found in other potentially wet locations,
such as exterior outlets or those in a laundry

00:01:26.090 --> 00:01:29.740
room or garage, will usually require protection
as well.

00:01:29.740 --> 00:01:33.740
The theory is that you’re much more likely
to experience an electric shock near water,

00:01:33.740 --> 00:01:37.710
‘cause water tends to conduct electricity
pretty well and thus if your hands are wet

00:01:37.710 --> 00:01:42.630
or a power cord is wet, you’re at a significantly
higher risk of electric shock when touching

00:01:42.630 --> 00:01:44.290
anything remotely electrical.

00:01:44.290 --> 00:01:48.429
Anyway, how do these devices determine if
a shock might be happening, and thus how do

00:01:48.429 --> 00:01:50.159
they know they need to break the circuit?

00:01:50.159 --> 00:01:52.700
Well, part of the answer is in the name.

00:01:52.700 --> 00:01:58.039
The Americaspeak version, ground-fault circuit
interrupter, suggests it can detect some problem

00:01:58.039 --> 00:01:59.789
related to the ground.

00:01:59.789 --> 00:02:04.409
The most-other-places name, Residual Current
Device, suggests current is going somewhere

00:02:04.409 --> 00:02:05.409
it shouldn’t.

00:02:05.409 --> 00:02:09.380
I’ve always felt that both of these names
compliment the other and make the issue easier

00:02:09.380 --> 00:02:12.680
to understand, but on their own they’re
somewhat inadequate.

00:02:12.680 --> 00:02:17.220
Residual current is kinda the result of a
ground fault, but what does that even mean?

00:02:17.540 --> 00:02:21.580
Well, in any ordinary circumstance, the current
flowing out of one side of the outlet will

00:02:21.580 --> 00:02:24.830
exactly match the current flowing back into
the other.

00:02:24.830 --> 00:02:27.340
There should always be a balance in an electric
circuit

00:02:27.340 --> 00:02:30.220
between the hot supply and the neutral return.

00:02:30.220 --> 00:02:34.070
If you plug in a toaster, then for every unit
of current flowing towards the toaster in

00:02:34.070 --> 00:02:38.450
this wire, there is an equal unit of current
flowing away from it in the other.

00:02:38.450 --> 00:02:41.850
The same holds true for the reverse polarity
of the A/C cycle.

00:02:41.850 --> 00:02:45.910
But if I were to get an electric shock from
the toaster, perhaps by being a complete fool

00:02:45.910 --> 00:02:51.030
and sticking a knife down there like you should
never ever do, kids, then some of the current

00:02:51.030 --> 00:02:54.440
coming from the outlet gets diverted through
my body.

00:02:54.440 --> 00:02:58.000
Now, the current leaving the outlet is greater
than the current returning,

00:02:58.000 --> 00:03:00.520
because some of it doesn’t actually return.

00:03:00.520 --> 00:03:04.870
There is now an imbalance between the current
flowing out of the hot wire and back through

00:03:04.870 --> 00:03:06.400
the neutral wire.

00:03:06.400 --> 00:03:10.880
This fault condition is, from the outlet’s
perspective, a ground fault.

00:03:10.880 --> 00:03:14.560
Some of the current is not returning to ground,
or the neutral side.

00:03:14.560 --> 00:03:17.520
Somewhere outside the circuit, there is residual
current.

00:03:17.530 --> 00:03:21.050
See, both names work, but they describe the
problem differently.

00:03:21.050 --> 00:03:22.680
With a ground-fault detected,

00:03:22.680 --> 00:03:24.440
With residual
current detected,

00:03:24.440 --> 00:03:25.500
the device needs to

00:03:25.500 --> 00:03:27.170
interrupt the circuit.

00:03:27.170 --> 00:03:29.670
So it’s a ground fault circuit interrupter.

00:03:29.670 --> 00:03:31.740
So it’s a residual current device.

00:03:31.740 --> 00:03:36.030
As a side note, I like the term ground-fault
circuit interrupter better because it describes

00:03:36.030 --> 00:03:39.070
both what it detects and what it does.

00:03:39.070 --> 00:03:45.420
Even the 25% discount term, Ground Fault Interrupter,
describes both the problem and the action.

00:03:45.420 --> 00:03:49.620
Residual current device is a little incomplete
in describing its mission, but I will grant

00:03:49.620 --> 00:03:54.210
that residual current seems like a less-technical
description than ground-fault.

00:03:54.210 --> 00:03:55.080
But whatever.

00:03:55.080 --> 00:03:59.340
Now, I’ve always found the best way to show
how devices do what they do is to tear one apart.

00:03:59.340 --> 00:04:01.080
Off to the hardware store!

00:04:01.090 --> 00:04:02.310
I’m back!

00:04:02.310 --> 00:04:04.310
So let’s take a look at this thing.

00:04:04.310 --> 00:04:08.560
Like any electrical outlet, is has terminals
for incoming hot and neutral, as well as a

00:04:08.560 --> 00:04:09.940
separate ground.

00:04:09.940 --> 00:04:11.900
But these ones here are a little interesting.

00:04:11.900 --> 00:04:15.990
See, most standard outlets have two pairs
of terminals as well, but they’re connected

00:04:15.990 --> 00:04:17.700
by this little tab.

00:04:17.700 --> 00:04:22.420
This electrically joins the two halves together,
so connecting just one pair of wires powers

00:04:22.420 --> 00:04:27.150
both sides of the outlet, and you easily can
daisy-chain outlets together within a circuit.

00:04:27.150 --> 00:04:32.370
However, if you break the tabs off, now each
outlet is wired separately.

00:04:32.370 --> 00:04:37.190
This is often done so that one pair of plugs
can have two functions, with one side on a

00:04:37.190 --> 00:04:40.420
light switch for a lamp, and the other on
all the time.

00:04:40.420 --> 00:04:44.870
But the second set of terminals on a GFCI
is protected by its internal circuitry.

00:04:44.870 --> 00:04:47.800
That’s why they are labeled LINE and LOAD.

00:04:47.800 --> 00:04:52.051
Incoming power goes into the LINE terminals,
and any outlets farther down the circuit that

00:04:52.051 --> 00:04:56.910
are attached to the LOAD terminals will also
become ground-fault protected.

00:04:56.910 --> 00:05:00.960
The practical upshot of this is that in a
chain of outlets on one circuit, only the

00:05:00.960 --> 00:05:03.790
first needs to be a GFCI receptacle.

00:05:03.790 --> 00:05:08.180
The rest downstream will all get protection,
though there is a limit to how many you can

00:05:08.180 --> 00:05:12.150
string along depending on national and local
electric codes.

00:05:12.150 --> 00:05:16.910
One little curiosity is that most outlets
of this type can interrupt 20 amps, so although

00:05:16.910 --> 00:05:22.210
this is only a 15 amp receptacle, it can be
placed in a 20 amp circuit and provide protection

00:05:22.210 --> 00:05:24.090
for other 20 amp receptacles.

00:05:24.090 --> 00:05:25.600
So, let’s open it up.

00:05:25.600 --> 00:05:29.610
With everything removed we find the four screw
terminals mounted to a circuit board.

00:05:29.610 --> 00:05:34.370
These braided copper wires are carrying current
from the line side through to the load side,

00:05:34.370 --> 00:05:39.310
and the top pair of switch contacts would
normally energize the pins of the actual receptacle,

00:05:39.310 --> 00:05:42.390
which when assembled lie far above the circuit
board.

00:05:42.390 --> 00:05:46.380
This nylon bracket can move back and forth,
and it forms the actual switch that will break

00:05:46.380 --> 00:05:48.540
the circuit in a fault condition.

00:05:48.540 --> 00:05:52.780
It rests in the closed condition with the
help of a latch, and a spring down below will

00:05:52.780 --> 00:05:57.400
keep it in the open position once enough force
is exerted on it to overcome the latch.

00:05:57.400 --> 00:06:02.210
Now, this black cylinder piece is a tightly
wound coil of wire called a solenoid, and

00:06:02.210 --> 00:06:05.920
when current is passed through it it creates
a magnetic field which will force an iron

00:06:05.920 --> 00:06:08.690
plunger out of it in this direction.

00:06:08.690 --> 00:06:12.260
This plunger isn’t visible but it is what
breaks the circuit.

00:06:12.260 --> 00:06:16.450
When the electronics detect a ground fault,
they divert power into the solenoid which

00:06:16.450 --> 00:06:19.600
will push the plunger forward and thus kill
the power.

00:06:19.600 --> 00:06:21.840
But how does it detect current leakage?

00:06:21.840 --> 00:06:26.070
Well, look closely at the path the electricity
takes from the line connections through to

00:06:26.070 --> 00:06:27.669
the switch contacts.

00:06:27.669 --> 00:06:32.820
It goes via these busbars through a round
doo-dad, and if we move this varistor out

00:06:32.820 --> 00:06:36.550
of the way we can see that inside is a coil
of wire.

00:06:36.550 --> 00:06:40.470
This is the sense coil, and if you look on
the bottom you find that this is what is being

00:06:40.470 --> 00:06:41.480
monitored.

00:06:41.480 --> 00:06:46.230
You can see that IC1 has its pins connected
to the output of the coil, with some support

00:06:46.230 --> 00:06:47.740
components peppered in.

00:06:47.740 --> 00:06:50.139
And now we go back to school for a moment.

00:06:50.139 --> 00:06:54.890
You were likely taught that when current passes
through a wire, it generates a magnetic field.

00:06:54.890 --> 00:06:59.790
Likewise, when a magnetic field encounters
a wire, it induces a current in the wire.

00:06:59.790 --> 00:07:04.330
Basic stuff, but this is exactly the principle
that makes the GFCI work.

00:07:04.330 --> 00:07:09.050
See, in a normal condition, whatever unit
of current is going up through this side is

00:07:09.050 --> 00:07:11.770
also going down through that side.

00:07:11.770 --> 00:07:16.010
The current going to the toaster as before,
goes up this side, and the current coming

00:07:16.010 --> 00:07:18.810
back from it goes down that side.

00:07:18.810 --> 00:07:22.040
Of course that’s constantly switching back
and forth due to the fact that we’re dealing

00:07:22.040 --> 00:07:26.169
with A/C electricity, but they are always
opposite directions.

00:07:26.169 --> 00:07:30.610
Both bus bars generate a pretty sizeable magnetic
field around them depending of course on the

00:07:30.610 --> 00:07:36.230
load, but because they are going in opposite
directions the fields cancel each other out.

00:07:36.230 --> 00:07:40.410
That means that normally, no current is actually
induced in the sense coil.

00:07:40.410 --> 00:07:44.270
Even though there are two magnetic fields
being generated, they are of equal amount

00:07:44.270 --> 00:07:47.920
and opposite polarity, so the net result is
zero.

00:07:47.920 --> 00:07:52.570
But if there’s any imbalance at all between
the current going up one side and down the

00:07:52.570 --> 00:07:57.950
other, now the magnetic fields are no longer
in equal opposition and they don’t entirely

00:07:57.950 --> 00:07:59.240
cancel out.

00:07:59.240 --> 00:08:04.540
A tiny imbalance generates enough current
in the sense coil for the electronics to detect,

00:08:04.540 --> 00:08:08.980
and as soon as they do so the solenoid fires
and disconnects the circuit.

00:08:08.980 --> 00:08:13.180
Most devices like this are designed to break
the circuit in 30 milliseconds or less, and

00:08:13.180 --> 00:08:18.169
in the US they are designed to trip with only
5 milliamps of leakage current.

00:08:18.169 --> 00:08:20.330
So what’s the real-world use of this?

00:08:20.330 --> 00:08:21.330
Let me show you.

00:08:21.330 --> 00:08:24.080
A word of caution for the following demonstrations.

00:08:24.080 --> 00:08:25.800
What I’m doing is pretty dangerous.

00:08:25.800 --> 00:08:30.870
Energizing exposed terminals at line voltage
is not something you should casually do.

00:08:30.870 --> 00:08:33.890
Let me do the dangerous stuff, and please
don’t try this at home.

00:08:33.890 --> 00:08:38.769
I’ve wired up this naked GFCI to a plug
and I’ve put a few of things on its output.

00:08:38.769 --> 00:08:42.119
First, a standard light socket with a standard
bulb.

00:08:42.119 --> 00:08:46.770
Second, the same light socket but with an
adapter for an itty bitty bulb, and this one’s

00:08:46.770 --> 00:08:48.040
wired correctly.

00:08:48.040 --> 00:08:53.230
And third, the same light socket and adapter,
but this time it’s wired incorrectly.

00:08:53.230 --> 00:08:55.350
So right now, everything looks good.

00:08:55.350 --> 00:08:59.330
The current exiting the plug always matches
the current returning, so the electronics

00:08:59.330 --> 00:09:02.139
don’t intervene and the light stays lit.

00:09:02.139 --> 00:09:06.449
Now I’m going to screw this little 5 watt
bulb into the top light socket.

00:09:06.449 --> 00:09:08.880
Nothing happens, it just comes on.

00:09:08.880 --> 00:09:11.629
But now I’ll tighten the light on the bottom.

00:09:11.629 --> 00:09:16.920
As soon as it makes contact, the electronics
in the GFCI intervene, firing the solenoid,

00:09:16.920 --> 00:09:18.470
and breaking the circuit.

00:09:18.470 --> 00:09:19.470
But why?

00:09:19.470 --> 00:09:23.180
Well, the second light socket was wired with
a deliberate ground fault.

00:09:23.180 --> 00:09:28.130
I attached its hot wire to the monitored output
of the GFCI just like the the first one, but

00:09:28.130 --> 00:09:32.640
its neutral wire was hooked into the supply
neutral of the outlet, therefore bypassing

00:09:32.640 --> 00:09:34.240
the sense coil.

00:09:34.240 --> 00:09:38.639
This meant that the current that flowed out
through this wire and into the bulb didn’t

00:09:38.639 --> 00:09:40.839
take the same path back to the outlet.

00:09:40.839 --> 00:09:45.420
It leaked out somewhere (in this case just
to here), and the outlet could detect the

00:09:45.420 --> 00:09:48.660
resulting current imbalance through the sense
coil.

00:09:48.660 --> 00:09:53.480
Even though this lamp is really small, passing
only 41 milliamps when it’s lit, the GFCI

00:09:53.480 --> 00:09:56.820
could immediately detect the fault and broke
the circuit.

00:10:15.260 --> 00:10:19.000
The second lamp is analogous to someone getting
an electric shock.

00:10:19.009 --> 00:10:22.600
Current flowed out of the outlet, but it didn’t
make its way back in.

00:10:22.600 --> 00:10:27.060
If this were a human body rather than a light
bulb, said human could be in for a

00:10:27.060 --> 00:10:28.920
shocking experience.

00:10:28.920 --> 00:10:33.279
But thanks to the GFCI, the fault condition
was immediately detected and the current flow

00:10:33.280 --> 00:10:34.620
was stopped.

00:10:35.980 --> 00:10:37.910
Let me show you how fast this happens.

00:10:37.910 --> 00:10:41.769
I’ve disconnected the return wire so I can
just push it against the contacts.

00:10:41.769 --> 00:10:47.220
If I go to this contact nothing happens because
the current is taking the correct path to ground.

00:10:47.220 --> 00:10:50.600
The current returning from the bulb goes through
the sense coil.

00:10:50.610 --> 00:10:55.730
But if I just barely brush against the incoming
neutral connection, causing the return current

00:10:55.730 --> 00:11:00.889
to flow outside the sense coil, it detects
the imbalance imperceptibly quickly.

00:11:00.889 --> 00:11:02.589
And that’s why these are life savers.

00:11:02.589 --> 00:11:06.660
Imagine you’ve plugged your hair dryer into
the outlet in your bathroom, and the cord

00:11:06.660 --> 00:11:07.889
is frayed.

00:11:07.889 --> 00:11:11.959
You might have never noticed it, but if you
touched that wire with a wet hand you’d

00:11:11.959 --> 00:11:14.010
be in for a nasty shock.

00:11:14.010 --> 00:11:18.189
But if plugged into a ground fault interrupter,
almost immediately the current flow would

00:11:18.189 --> 00:11:21.290
be stopped and your life may very well have
been saved.

00:11:21.290 --> 00:11:24.820
And that’s why most modern devices that
are going to be used in the bathroom,

00:11:24.820 --> 00:11:26.000
like a hair dryer,

00:11:26.000 --> 00:11:30.429
are required to have a GFCI
built into their power plugs here in the US.

00:11:30.429 --> 00:11:34.680
There are plenty of older homes without GFCI
equipped receptacles,

00:11:34.680 --> 00:11:37.059
and for these your-hands-will-definitely-be-wet

00:11:37.059 --> 00:11:39.619
scenarios, it’s better safe than sorry.

00:11:39.619 --> 00:11:41.200
And now, some other things!

00:11:41.200 --> 00:11:45.000
First, in the US, these generally are NOT
circuit breakers.

00:11:45.920 --> 00:11:49.380
OK, yes they are, but I mean they don’t
protect against short circuits

00:11:49.380 --> 00:11:50.960
or excessive current.

00:11:50.960 --> 00:11:55.300
They are not a replacement for a traditional
circuit breaker but are instead a supplement

00:11:55.309 --> 00:11:56.319
to them.

00:11:56.320 --> 00:12:00.900
They do not duplicate the overcurrent protection
of your standard circuit breaker or fuse.

00:12:00.900 --> 00:12:04.760
Many GFCI receptacles here in the US have
an LED to indicate...

00:12:04.760 --> 00:12:06.000
something.

00:12:06.010 --> 00:12:08.879
The state that is being indicated is entirely
nonstandard.

00:12:08.879 --> 00:12:12.809
Many, such as these, have a light indicating
that it’s working.

00:12:12.809 --> 00:12:16.119
Presumably that light would go out if the
protection has failed.

00:12:16.119 --> 00:12:20.059
But I’ve also seen plugs where the light
is normally out, but comes on when the outlet

00:12:20.059 --> 00:12:21.529
has tripped!

00:12:21.529 --> 00:12:25.779
And these ones in my kitchen are normally
green and are off when tripped, but when you

00:12:25.779 --> 00:12:28.319
reset them, they briefly illuminate red.

00:12:28.319 --> 00:12:32.790
So probably, they would light up red if the
protection circuit had failed.

00:12:32.790 --> 00:12:33.790
Which does happen.

00:12:33.790 --> 00:12:36.720
That’s why they are all labeled “TEST
MONTHLY”.

00:12:36.720 --> 00:12:40.759
And the neat thing about the test is that
this actually creates a ground fault!

00:12:40.759 --> 00:12:45.309
You might have noticed this resistor apparently
randomly sticking up from the circuit board.

00:12:45.309 --> 00:12:49.959
This resistor creates a path to the incoming
neutral, and pressing the TEST button shunts

00:12:49.959 --> 00:12:52.480
this resistor to the monitored hot.

00:12:52.480 --> 00:12:56.319
So by pressing the TEST button, you are for
real testing its ability to detect a ground

00:12:56.319 --> 00:13:00.630
fault because you actually are creating a
ground-fault internally.

00:13:00.630 --> 00:13:04.839
Even better, the resistor is sized to roughly
match the minimum leakage it’s designed

00:13:04.839 --> 00:13:05.940
to detect.

00:13:05.940 --> 00:13:10.329
So definitely test these periodically, especially
since leaving them in the non-tripped position

00:13:10.329 --> 00:13:15.509
for a couple of dozen years might make them
mechanically seized up and prevent them from

00:13:15.509 --> 00:13:17.890
doing their job should the need arise.

00:13:17.890 --> 00:13:21.809
You might be wondering why we in the US put
these in outlet boxes when others put them

00:13:21.809 --> 00:13:23.529
in service panels.

00:13:23.529 --> 00:13:26.000
Well there’s pros and cons to each method.

00:13:26.000 --> 00:13:30.739
Doing it in the US fashion makes it obvious
if any installation is up to code, as a lack

00:13:30.739 --> 00:13:35.600
of GFCI outlets in a bathroom or kitchen means
an obvious fail.

00:13:35.600 --> 00:13:40.369
It also probably encourages testing if the
device is easy to access rather than being

00:13:40.369 --> 00:13:42.050
part of a circuit breaker panel.

00:13:42.050 --> 00:13:46.139
However, there is a benefit to having this
protection in all areas of the home.

00:13:46.139 --> 00:13:50.560
Sure, an electric shock is more likely in
wet places, but it’s not like no one has

00:13:50.560 --> 00:13:52.829
ever received a shock in their bedroom or
whatever.

00:13:52.829 --> 00:13:57.819
Plus, in many countries, residual current
devices are combined with circuit breakers,

00:13:57.819 --> 00:14:03.959
forming one device called an RCBO, for Residual
Current circuit-Breaker with Overcurrent protection.

00:14:03.959 --> 00:14:08.410
But putting the protection in the service
panel makes troubleshooting a whole lot harder.

00:14:08.410 --> 00:14:12.809
If something malfunctions and causes a ground
fault anywhere in the circuit, you might be

00:14:12.809 --> 00:14:17.680
spending a long time determining what device
is actually causing the fault.

00:14:17.680 --> 00:14:21.089
Putting the protection at the outlet makes
it rather obvious.

00:14:21.089 --> 00:14:24.720
One thing that I discovered when tearing this
apart is that the internal contacts are able

00:14:24.720 --> 00:14:28.149
to accomodate a NEMA 5-20 plug.

00:14:28.149 --> 00:14:33.369
Normally US devices that require 20 amps will
have this plug where one pin is sideways,

00:14:33.369 --> 00:14:36.550
thus preventing you from plugging it into
a 15 amp circuit.

00:14:36.550 --> 00:14:41.399
The fact that this device has internal pins
capable of accepting this plug, plus the fact

00:14:41.399 --> 00:14:46.480
that it can break 20 amps as most GFCI outlets
can, means the only thing preventing this

00:14:46.480 --> 00:14:53.730
receptacle from actually being a 20 amp receptacle
is the shape of the holes on the plastic faceplate.

00:14:53.730 --> 00:14:58.420
Which means that, in the case of this particular
model anyway, they charge you $3 more for

00:14:58.420 --> 00:15:02.170
the same product with a slightly different
piece of plastic on the front.

00:15:02.170 --> 00:15:03.170
Yay.

00:15:03.170 --> 00:15:06.720
And finally, though these are super helpful
at reducing the chance of injury or death

00:15:06.720 --> 00:15:11.319
due to an electric shock, they shouldn’t
be seen as an excuse to be reckless around

00:15:11.319 --> 00:15:12.350
electricity.

00:15:12.350 --> 00:15:17.129
They are a very effective safety net, but
why risk falling in the first place?

00:15:17.129 --> 00:15:20.690
That said, if you’re a tinkerer who likes
to work on electronics, installing one of

00:15:20.690 --> 00:15:23.920
these in your workshop might be a very good
investment.

00:15:23.920 --> 00:15:27.060
At the very least, it might spare you the
pain of a zap.

00:15:27.060 --> 00:15:28.880
Thanks for watching, I hope you enjoyed the
video!

00:15:28.880 --> 00:15:32.459
If this is your first time coming across the
channel and you liked what you saw, please

00:15:32.459 --> 00:15:34.119
consider subscribing!

00:15:34.119 --> 00:15:38.250
As always, thank you to everyone who supports
this channel on Patreon, especially the fine

00:15:38.250 --> 00:15:41.009
folks that are scrolling up your screen.

00:15:41.009 --> 00:15:43.959
Patrons of the channel are what keep these
videos coming, and if you’re interested

00:15:43.959 --> 00:15:46.640
in pledging some support for the channel and
helping it to grow,

00:15:46.640 --> 00:15:48.680
please check out my Patreon page.

00:15:48.680 --> 00:15:51.340
Thank you for your consideration, and I’ll
see you next time!

